5-272
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
ECOM100 Configuration (ECOM100) (IB-710)
ECOM100 Configuration defines all the common information for one specific ECOM100
module which is used by the other ECOM100 IBoxes; for example, ECRX - ECOM100
Network Read, ECEMAIL - ECOM100 Send EMail, ECIPSUP - ECOM100 IP Setup, etc.
You MUST have the ECOM100 Configuration IBox at the top of your ladder/stage program
with any other configuration IBoxes. The Message Buffer parameter specifies the starting
address of a 65 WORD buffer. This is 101 Octal addresses (e.g., V1400 thru V1500).
If you have more than one ECOM100 in your PLC, you must have a different ECOM100
Configuration IBox for EACH ECOM100 module in your system that utilizes any ECOM
IBox instructions.
The Workspace and Status parameters and the entire Message Buffer are internal, private
registers used by the ECOM100 Configuration IBox and MUST BE UNIQUE in this one
instruction and MUST NOT be used anywhere else in your program.
In order for MOST ECOM100 IBoxes to function, you must turn ON dip switch 7 on the
ECOM100 circuit board. You can keep dip switch 7 off if you are ONLY using ECOM100
Network Read and Write IBoxes (ECRX, ECWX).
ECOM100 Parameters
ECOM100#: this is a logical number
associated with this specific ECOM100
module in the specified slot. All other
ECxxxx IBoxes that need to reference this
ECOM100 module must reference this
logical number.
Slot: specifies which PLC slot is occupied by
the ECOM100 module.
Status: specifies a V-memory location that
will be used by the instruction.
Workspace: specifies a V-memory location
that will be used by the instruction.
Msg Buffer: specifies the starting address of a 65-word buffer that will be used by the module for
configuration.
DS5 Used
HPP
N/A
Parameter DL205 Range
ECOM100# ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ K K0-255
Slot ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ K K0-7
Status ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V See DL205 V-memory map - Data Words
Workspace ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V See DL205 V-memory map - Data Words
Msg Buffer (65 words used) ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V See DL205 V-memory map - Data Words
230
240
250-1
260