DL205 User Manual, 4th Edition, Rev. D
5-274
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
ECOM100 Disable DHCP (ECDHCPD) (IB-736)
ECOM100 Disable DHCP will set up the ECOM100 to use its internal TCP/IP settings on a
leading edge transition to the IBox. To configure the ECOM100’s TCP/IP settings manually,
use the NetEdit3 utility, or you can do it programmatically from your PLC program using
the ECOM100 IP Setup (ECIPSUP), or the individual ECOM100 IBoxes: ECOM Write IP
Address (ECWRIP), ECOM Write Gateway Address (ECWRGWA), and ECOM100 Write
Subnet Mask (ECWRSNM).
The Workspace parameter is an internal, private register used by this IBox and MUST BE
UNIQUE in this one instruction and MUST NOT be used anywhere else in your program.
Either the Success or Error bit parameter will turn on once the command is complete. If there
is an error, the Error Code parameter will report an ECOM100 error code (less than 100), or
a PLC logic error (greater than 1000).
The “Disable DHCP” setting is stored in Flash-ROM in the ECOM100 and the execution
of this IBox will disable the ECOM100 module for at least a half second until it writes the
Flash-ROM. Therefore, it is HIGHLY RECOMMENDED that you only execute this IBox
ONCE, on the second scan. Since it requires a LEADING edge to execute, use a NORMALLY
CLOSED SP0 (STR NOT First Scan) to drive the power flow to the IBox.
In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the
ECOM100 circuit board.
ECDHCPD Parameters
ECOM100#: this is a logical number associated with
this specific ECOM100 module in the specified
slot. All other ECxxxx IBoxes that need to reference
this ECOM100 module must reference this logical
number
Workspace: specifies a V-memory location that will
be used by the instruction
Success: specifies a bit that will turn on once the
request is completed successfully
Error: specifies a bit that will turn on if the
instruction is not completed successfully
Error Code: specifies the location where the Error
Code will be written
Parameter DL205 Range
ECOM100# ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ K K0-255
Workspace ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V See DL205 V-memory map - Data Words
Success ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B See DL205 V-memory map
Error ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B See DL205 V-memory map
Error Code ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V See DL205 V-memory map - Data Words
DS5 Used
HPP
N/A
230
240
250-1
260