DL205 User Manual, 4th Edition, Rev. D
5-276
Chapter 5: Standard RLL Instructions
1
2
3
4
5
6
7
8
9
10
11
12
13
14
A
B
C
D
ECOM100 Enable DHCP (ECDHCPE) (IB-735)
ECOM100 Enable DHCP will tell the ECOM100 to obtain its TCP/IP setup from a DHCP
Server on a leading edge transition to the IBox.
The IBox will be successful once the ECOM100 has received its TCP/IP settings from the
DHCP server. Since it is possible for the DHCP server to be unavailable, a Timeout parameter
is provided so that the IBox can complete, but with an Error (Error Code = 1004 decimal).
See also the ECOM100 IP Setup (ECIPSUP) IBox 717 to directly set up ALL of the TCP/IP
parameters in a single instruction - IP Address, Subnet Mask, and Gateway Address.
The Workspace parameter is an internal, private register used by this IBox and MUST BE
UNIQUE in this one instruction and MUST NOT be used anywhere else in your program.
Either the Success or Error bit parameter will turn on once the command is complete. If there
is an error, the Error Code parameter will report an ECOM100 error code (less than 100), or
a PLC logic error (greater than 1000).
The “Enable DHCP” setting is stored in Flash-ROM in the ECOM100 and the execution
of this IBox will disable the ECOM100 module for at least a half second until it writes the
Flash-ROM. Therefore, it is HIGHLY RECOMMENDED that you only execute this IBox
ONCE, on the second scan. Since it requires a LEADING edge to execute, use a NORMALLY
CLOSED SP0 (STR NOT First Scan) to drive the power flow to the IBox.
In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the
ECOM100 circuit board.
ECDHCPE Parameters
• ECOM100#: this is a logical number associated
with this specific ECOM100 module in the specified
slot. All other ECxxxx IBoxes that need to reference
this ECOM100 module must reference this logical
number.
• Timeout(sec): specifies a timeout period so that the
instruction may have time to complete.
• Workspace: specifies a V-memory location that will
be used by the instruction.
• Success: specifies a bit that will turn on once the
request is completed successfully.
• Error: specifies a bit that will turn on if the instruction is not completed successfully.
• Error Code: specifies the location where the Error Code will be written.
Parameter DL205 Range
ECOM100# ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ K K0-255
Timeout (sec) ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ K K5-127
Workspace ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V See DL205 V-memory map - Data Words
Success ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B See DL205 V-memory map
Error ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B See DL205 V-memory map
Error Code ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V See DL205 V-memory map - Data Words
DS5 Used
HPP
N/A
230
240
250-1
260