ECOM100 Query DHCP Setting (ECDHCPQ) (IB-734)
ECOM100 Query DHCP Setting will determine if DHCP is enabled in the ECOM100 on a
leading edge transition to the IBox. The DHCP Enabled bit parameter will be ON if DHCP
is enabled, OFF if disabled.
The Workspace parameter is an internal, private register used by this IBox and MUST BE
UNIQUE in this one instruction and MUST NOT be used anywhere else in your program.
Either the Success or Error bit parameter will turn on once the command is complete.
In order for this ECOM100 IBox to function, you must turn ON dip switch 7 on the
ECOM100 circuit board.
ECDHCPQ Parameters
• ECOM100#: this is a logical number associated
with this specific ECOM100 module in the
specified slot. All other ECxxxx IBoxes that
need to reference this ECOM100 module must
reference this logical number.
• Workspace: specifies a V-memory location that
will be used by the instruction.
• Success: specifies a bit that will turn on once the
instruction is completed successfully.
• Error: specifies a bit that will turn on if the
instruction is not completed successfully.
• DHCP Enabled: specifies a bit that will turn on if the ECOM100’s DHCP is enabled or remain
off if disabled - after instruction query, be sure to check the state of the Success/Error bit state along
with DHCP Enabled bit state to confirm a successful module query.
Parameter DL205 Range
ECOM100# ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ K K0-255
Workspace ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ V See DL205 V-memory map - Data Words
Success ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B See DL205 V-memory map
Error ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B See DL205 V-memory map
DHCP Enabled ⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠⸠ X,Y,C,GX,GY,B See DL205 V-memory map