Rung 2: When a machine goes down, send an email to Joe in maintenance and to the VP over
production showing what machine is down along with the date/time stamp of when it went
down.
The ECEMAIL is leading edge triggered, not power-flow driven (similar to a counter input
leg). An email will be sent whenever the power flow into the IBox goes from OFF to ON. This
helps prevent self-inflicted spamming.
If the EMail is sent, turn on C100. If there is a failure, turn on C101. If it fails, you can look
at V2000 for the SMTP error code or other possible error codes.
ECEMAIL Example
Rung 1: The ECOM100 Config IBox is responsible for coordination/interlocking of all
ECOM100 type IBoxes for one specific ECOM100 module. Tag the ECOM100 in slot 1 as
ECOM100# K0. All other ECxxxx IBoxes refer to this module # as K0. If you need to move
the module in the base to a different slot, then you only need to change this one IBox. V400 is
used as a global result status register for the other ECxxxx IBoxes using this specific ECOM100
module.V401 is used to coordinate/interlock the logic in all of the other ECxxxx IBoxes using
this specific ECOM100 module. V402-V502 is a common 130-byte buffer available for use by
the other ECxxxx IBoxes using this specific ECOM100 module.
NOTE: An ECOM100 IBox instruction is used without a permissive contact. The top line will be identified in
BOLD italics, and the instruction name and ID will be in BOLD characters.