Benning ST 755+ - Factory Settings and Measured Values - Current Measuring Method; Table 49 Measured Values According to Measuring Specifications - Insulating Resistance Tests; Table 50 Factory Settings of the Limits for Protective Conductor Current Test; Table 51 Factory Settings of the Limits for Contact Current Test

Benning ST 755+
124 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
13.4 Factory settings and measured values
5284 / 08/2023 en BENNING ST 755+ / ST 760+ 113
Parameter Value
Testing current >1mA at 500kΩ and 500V‑DC
<5mA at 0Ω and 500V‑DC
<7mA at 0Ω and 1 000V‑DC
Measuring range 0.10... 100MΩ
Resolution 0.01MΩ
Accuracy ±15% of the measured value
Table49: Measured values according to measuring specifications– Insulating resistance tests
13.4.3 Factory settings and measured values– Current
measuring method
Test Value Unit
I
PE
VDE0701/0702, devices in general 3.5 mA
I
PE
VDE0701/0702, with heating elements >3.5kW 1.0 (max.10mA) mA/kW
I
PE
VDE0544-4, ClassI 10.0 mA
Table50: Factory settings of the limits for protective conductor current test
Test Value Unit
I
Cont
VDE0701/0702 0.5 mA
I
Cont
VDE0544-4 0.5 mA
I
Cont
VDE0544-4 welding output 10.0 mA
Table51: Factory settings of the limits for contact current test
Test Value Unit
I
Leak
VDE0751-1, ClassI 0.5 mA
I
Leak
VDE0751-1, ClassII 0.1 mA
I
PLeak
VDE0751-1, ClassI, AC, typeBF 5.00 mA
I
PLeak
VDE0751-1, ClassI, AC, typeCF 0.05 mA
I
PLeak
VDE0751-1, ClassI, DC, typeBF 0.01 mA
I
PLeak
VDE0751-1, ClassI, DC, typeCF 0.01 mA
I
PLeak
VDE0751-1, ClassII, AC, typeBF 5.00 mA
I
PLeak
VDE0751-1, ClassII, AC, typeCF 0.05 mA
I
PLeak
VDE0751-1, ClassII, DC, typeBF 0.01 mA
I
PLeak
VDE0751-1, ClassII, DC, typeCF 0.01 mA
Table52: Factory settings of the limits for leakage current test
Parameter Value
Measuring range 0.03... 25mA
Resolution 0.001mA
Accuracy ±15% of the measured value
Internal resistance
(measuring instrument/
probe)
VDE0701/0702: R
i
= 1kΩ
VDE0751-1: R
i
= 1kΩ
VDE0544: R
i
= 2kΩ
Table53: Protective conductor resistance– Alternative leakage current measuring method
Parameter Value
Measuring range 0.05...25mA