InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp – January 2016 111
AMF26-P-2.4 Reference Guide.pdf
Condition of the transition
FUEL SOLENOID on
4
MaxCrank Time counter
started
D+ input activated or oil pressure detected
or Gen voltage > 25% Vgnom or D+ active
for 1s
MaxCrank Time elapsed, 1st attempt
STARTER off
FUEL SOLENOID off
STOP SOLENOID on
CrankFail Pause timer
started
MaxCrank Time elapsed, last attempt
STARTER on
FUEL SOLENOID on
4
STOP SOLENOID off
MaxCrank Time counter
started
READY TO LOAD on
1
Min, Max Stab Time
counter started
RPM = 0 or any other shutdown condition
FUEL SOLENOID off
STOP SOLENOID on
FUEL SOLENOID off
STOP SOLENOID on
READY TO LOAD off
Cooling Time timer
started
RPM = 0 or any other shutdown condition
READY TO LOAD off
2
FUEL SOLENOID off
RPM = 0 or any other shutdown condition
FUEL SOLENOID off
STOP SOLENOID on
READY TO LOAD off
FUEL SOLENOID off
STOP SOLENOID on
RPM = 0 or any other shutdown condition
FUEL SOLENOID off
STOP SOLENOID on
RPM = 0, Oil pressure not detected, Vgen <
10V, D+ not active
1
if all generator parameters OK and Min Stab Time elapsed, indicates that GCB is possible to close.
In AUTO Mode closes in this moment GCB automatically.