InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp – January 2016 51
AMF26-P-2.4 Reference Guide.pdf
After the input is open again, the controller recovers to previous state and behaves according to the
actual situation .
Function is active in any controller mode.
Start Button
Binary input has the same function as START BUTTON on the IL-NT front panel. It is active in MAN
mode only.
Stop Button
Binary input has the same function as STOP BUTTON on the IL-NT front panel. It is active in MAN
Mode only.
Hint:
Changed function of Stop Button. After the first pressing from running state, there is a standard delay
and controller change state to cooling. After holding the button down for 2 seconds controller goes to
stop state. The same holds true for BI “Stop Button”.
FaultResButton
Binary input has the same function as FAULT RESET button on the IL-NT front panel.
HornResButton
This binary input can be used for horn resetting. When Horn binary output is active it can be
deactivated by activating HornResButton input.
GCB Button
Binary input has the same function as GCB button on the IL-NT front panel. It is active in MAN mode
only.
MCB Button
Binary input has the same function as MCB button on the IL-NT front panel. It is active in MAN mode
only.
MainsFailBlock
If the input is closed, the automatic start of the gen-set at Mains failure is blocked and in case of
running gen-set (after MFB MReturnDel) the GCB is opened, MCB is closed and gen-set goes to
Cooling procedure and stops. The input simulates healthy Mains.
Lang Selection
Not configured
Language selection is done only through the controller display. Pressing ENTER and PAGE buttons
concurrently and then only PAGE button separately.
Configured on any binary input
If the input is opened the first (default) language is active and if the input is closed then the second
language is active. In case there is more languages available in the controller it is not possible to
select any other language even through the controller display.
Preheating
When controller receives information that engine preheating is active (binary input PREHEATING is
active) at the moment of Start request, then (after prestart period is finished) prestart timer remains at
0 and Start sequence is blocked till the moment the Preheating is deactivated.
Hint:
To secure proper functionality of this function Engine Params: Prestart Time has to be set for at least
1 second (Prestart Time >= 1) otherwise there might be not enough time to block the start sequence.