EasyManua.ls Logo

ComAp InteliLite NT AMF26-P - Event Messages Description

ComAp InteliLite NT AMF26-P
167 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp January 2016 147
AMF26-P-2.4 Reference Guide.pdf
Example 5 reading and writing other type
SMS:
#5:accesscode r8235,w8296 110.2
read value 8235,
write 110.2 with decimal point
Answer:
#Gen-set name:OIIIOOIIO,ok
read value of 8235 (binary value),
writing was ok
Note: 1. Writing of binary setpoint is not supported.
2. Writing of setpoint with decimal point is automatically converted to
appropriate number of decimal places.
Example 6 reading actual Alarm list
SMS:
#5:accesscode a
read actual Alarm list
Answer:
#Gen-set name:AL=(!Wrn PrimWater
temp, !Wrn SecWater temp, Batt volt)
Actual Alarm list contains three
items.
Event messages description
Following events can be received by mobile phone.
o Manual Start
o Manual Stop
o Remote Start
o Remote Stop
o AMF Start
o AMF Stop
o Mains Fail
o Mains Returned
o Load on Mains (when MCB is closed)
o Load on Genset (when GCB is closed)
Message structure for controller with RTC
Genset Name [10:15:24 06.04.2011]
10:15:15 Mains Fail
10:15:18 AMF Start
10:15:22 Mains Returned
10:15:23 Load on Mains
10:15:24 AMF Stop
Message structure for controller without RTC
Genset Name [5896:30]
5896:29 Mains Fail
5896:29 AMF Start
5896:30 Mains Returned
5896:30 Load on Mains
5896:30 AMF Stop
Hint:
Event message is sent, if there is no other event. within 30s, any additonal delay could be caused by
local provider.