AMF26-P-2.4 Reference Guide.pdf
Example 5 – reading and writing other type
#5:accesscode r8235,w8296 110.2
read value 8235,
write 110.2 with decimal point
#Gen-set name:OIIIOOIIO,ok
read value of 8235 (binary value),
writing was ok
Note: 1. Writing of binary setpoint is not supported.
2. Writing of setpoint with decimal point is automatically converted to
appropriate number of decimal places.
Example 6 – reading actual Alarm list
#Gen-set name:AL=(!Wrn PrimWater
temp, !Wrn SecWater temp, Batt volt)
Actual Alarm list contains three
items.
Event messages description
Following events can be received by mobile phone.
o Manual Start
o Manual Stop
o Remote Start
o Remote Stop
o AMF Start
o AMF Stop
o Mains Fail
o Mains Returned
o Load on Mains (when MCB is closed)
o Load on Genset (when GCB is closed)
Message structure for controller with RTC
Genset Name [10:15:24 06.04.2011]
10:15:15 Mains Fail
10:15:18 AMF Start
10:15:22 Mains Returned
10:15:23 Load on Mains
10:15:24 AMF Stop
Message structure for controller without RTC
Genset Name [5896:30]
5896:29 Mains Fail
5896:29 AMF Start
5896:30 Mains Returned
5896:30 Load on Mains
5896:30 AMF Stop
Hint:
Event message is sent, if there is no other event. within 30s, any additonal delay could be caused by