AMF26-P, SW version 2.4, ©ComAp – January 2016 116
AMF26-P-2.4 Reference Guide.pdf
Alarm Management
Following alarms are available:
x Sensor Fail
x Warning
x Breaker open and cooling
x Shut down
x Mains failure
Sensor Fail (FLS)
Sensor Fail is detected when measured value is 6% out of selected sensor characteristic, or data from
ECU is missing. Sensor Fail is indicated by ##### symbol instead measured value.
Warning (WRN)
When warning comes up, only alarm outputs and common warning output are closed.
Possible warnings:
See List of possible events
Breaker open and cooling (BOC)
When the BOC alarm comes up, IL-NT opens first output GCB CLOSE/OPEN (as well as binary
output BREAKER TRIP is activated) to unload the gen-set and then after cooling time it also stops the
gen-set. Alarm outputs and common shutdown output are activated. Active or not acknowledged
protection disables gen-set start.
Possible BOC alarms:
See List of possible events
Shut down (SD)
When the shut-down alarm comes up, IL-NT opens outputs GCB CLOSE/OPEN, FUEL SOLENOID,
STARTER and PRESTART to stop the engine immediately. Alarm outputs and common shutdown
output are closed. Active or not reset protection disables start.
Possible shut-down alarms:
See List of possible events
Mains failure (MF)
Mains failure detection depends on Auto mains failure setpoints (levels and delays) adjusting. When
the mains failure comes up, mains circuit breaker is opened.
Possible mains failure reasons:
See List of possible events