AMF26-P-2.4 Reference Guide.pdf
Recommended Wiring
AMF - Wiring Diagram
LOAD
ACCES S L OCK
EMERGENCY STO
P
CONTRO
L
SIGNALS
GEN C.B. FEED-BACK
MAINS C.B. FEED
-BA
CK
DIESEL/GAS ENGINE
RPM
GENERATOR
G
+24 V
L1
L2
L3
N
Generator C.B.
Mains C.B.
SPRINKL ER
REMOTE TEST
RS-232C
Interface
Modem or PC
REMOTE OFF
ALARM
BINARY OUTPUTS
MAINS C.B
.
GEN
C
.B
.
PRESTART
READY TO LOA D
O
I
L
P
R
E
S
S
U
R
E
W
A
T
E
R
T
E
M
P
F
U
E
L
L
E
V
E
L
S
T
A
R
T
E
R
B
A
T
T
E
R
Y
-
+
F
U
E
L
S
O
L
E
N
O
I
D
D+
F
U
E
L
S
O
L
E
N
O
I
D
S
T
A
R
T
E
R
ECU
In case of the wiring above following setting should be used.
ConnectionType: 3Ph4Wire, CT location: Gen-Set and Number of CTs: 3CTs
Hint:
MCB and GCB is recommended to be mechanically interlocked.
It is possible to start Volvo and Scania engines via CAN bus. See Engines started via CAN bus.