AMF26-P, SW version 2.4, ©ComAp – January 2016 82
AMF26-P-2.4 Reference Guide.pdf
If the analog value goes over or under limit of analog input, delay setpoint is not evaluated and genset
triggers the protection when IDLE time is elapsed.
BI6 Delay [s]
Delay for binary input number 6.
Step: 0,1 s
Range: 0 – 3600 s
BI7 Delay [s]
Delay for binary input number 7.
Step: 0,1 s
Range: 0 – 3600 s
Hint:
There is a possibility to set programmable delay on alarms configured for binary output 6 and/or 7. If
set, it blocks alarms of the respective binary input all the time when the delay is active. If the reason
for the alarm persists after the delay elapses, the alarm is activated. If not, the alarm is not activated.
This feature allows user to perform “filtering” of alarms.
Batt Undervolt [V]
Warning threshold for low battery voltage.
Step: 0,1 V
Range: 8V – 40 (Battery >Volts)
Batt Overvolt [V]
Warning threshold for hi battery voltage.
Step: 0,1 V
Range: 8V – 40 (Battery <Volts)
Batt Volt Del [s]
Delay for low battery voltage alarm.
Step: 1s
Range: 0 – 600 s
Maintenance [h]
Counts down when engine running. If reaches zero, an alarm appears. When the value 10000 is set,
than the Maintenance function is disabled and counter does not count. Counter value disappears in
controllers statictics.
Step: 1h
Range: 0 –10000h
Gener Protect
All electric protections when activated result in shutdown.
Overload BOC [%]
Threshold for generator overload (in % of Nominal power)
Step: 1% of Nominal power
Range: 0 – 200%
Overload Del [s]
Delay for generator overload alarm.
Step: 0,1s
Range: 0 – 600,0 s