InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp – January 2016 81
AMF26-P-2.4 Reference Guide.pdf
Step: 1% of nominal RPM
Range: 100 – 150%
Hint:
The Overspeed protection value is increasing from 115 % to 125% of nominal RPM for the duration
of 5sec (ProtectHoldOff delay). ProtectHoldOff delay takes place during the start of the gen-set when
some engine protections have to be blocked. This delay starts after reaching 25% of nominal RPM. It
holds true if the value GeerTeeth = 0.
AI1 Wrn [Bar]
Warning threshold level for ANALOG INPUT 1
Step: 0,1 bar
Range: -10 – 1000
AI1 Sd [Bar]
Shutdown threshold level for ANALOG INPUT 1
Step: 0,1 bar
Range: -10 – 1000
AI1 Del [s]
Delay for ANALOG INPUT 1
Step: 1 s
Range: 0 – 900 s
AI2 Wrn [ ]
Warning threshold level for ANALOG INPUT 2
Step: 1 qC
Range: -100 – 10000
AI2 Sd [ ]
Shutdown threshold level for ANALOG INPUT 2
Step: 1 qC
Range: -100 – 10000
AI2 Del [s]
Delay for ANALOG INPUT 2 alarm.
Step: 1 s
Range: 0 – 900 s
AI3 Wrn [ ]
Warning threshold level for ANALOG INPUT 3
Step: 1 %
Range: -100 – 10000
AI3 Sd [ ]
Shutdown threshold level for ANALOG INPUT 3
Step: 1 %
Range: -100 – 10000
AI3 Del [s]
Delay for ANALOG INPUT 3
Step: 1 s
Range: 0 – 900 s