InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp January 2016 91
AMF26-P-2.4 Reference Guide.pdf
Hint:
This option should be used for MCBs using 230V control and not equipped with the undervoltage coil.
Date/Time
Time Stamp Per [min]
Time interval for periodic history records.
Step: 1 min
Range: 0 200min
Hint:
Time stamps are only recorded into history while gen-set is running. There are no time stamps records
made when engine is stopped.
#SummerTimeMod [DISABLED / WINTER / SUMMER/WINTER-S
/ SUMMER-S]
DISABLED: Automatic switching between summer and wintertime is disabled.
WINTER (SUMMER) : Automatic switching between summer and wintertime is enabled and it
is set to winter (summer) season.
WINTER-S (SUMMER-S) : Modification for southern hemisphere.
#Time [HHMMSS]
Real time clock adjustment.
#Date [DDMMYYYY]
Actual date adjustment.
Timer1..3Function [No Func/TEST/TEST OnLd/MFail Blk/Mode OFF]
It is possible to choose out of 5 following Timer functions. Binary output TIMER is always activated
when Timer is active regardless of chosen Timer function.
No Func: There is no any other function, but binary output TIMER1..3 activation.
TEST: When this option is chosen then the Timer output is also internally connected to the
REMOTE TEST binary input.
TEST OnLd: When this option is chosen then the Timer output is also internally connected to the
REM TEST ONLD binary input.
MFail Blk: When this option is chosen then the Timer output is also internally connected to the
MAINSFAILBLOCK binary input.
Mode OFF: When this option is chosen then the Timer output is also internally connected to the
REMOTE OFF binary input.
Timer1..3 Repeat
[NONE/MONDAY/TUESDAY/WEDNESDAY/THURSDAY/WEDNESDAY/FRI
DAY/SATURDAY/SUNDAY/MON-FRI/MON-SAT/MON-SUN/SAT-SUN/SUN-
MON/12 Hours/8 Hours/6 Hours/4 Hours/3 Hours/2 Hours/1 Hour]
Defines time of TIMER 1..3 activation.
NONE:
Timer function is disabled
MONDAY, TUESDAY, WEDNESDAY, THURSDAY, WEDNESDAY, FRIDAY, SATURDAY, SUNDAY:
Timer is activated on daily basis.
MON-FRI, MON-SAT, SAT-SUN, SUN-MON: