If GCB output used GCB opens automatically
3
The start-up sequence can be interrupted in any time by comming stop request
4
Fuel solenoid is switched on with time advance of 1s fixed before starter motor is switched on.
Hint:
Threshold level for D+ input is 80% supply voltage, activation delay is 1s (to override short firings
during cranking for example in cold conditions).
AUT Mode
The controller does not respond to buttons START, STOP, MCB ON/OFF, GCB ON/OFF. Engine
start/stop request is evaluated form Mains failure/return.
AMF sequence (simplified)
State
Condition of the transition
Action
Next state
Mains
operation
Mains failed
1
or MCB feedback dropout
MCB Opens On = MAINSFAIL
MCB CLOSE/OPEN off
EmergStart Del timer
started
Mains failure
Mains failed
1
or MCB feedback dropout
MCB Opens On = GENRUN
EmergStart Del timer
started
Mains failure
Mains
failure
Mains voltage and frequency OK
MCB Opens On = MAINSFAIL
After elapsing MCB Close
Del MCB CLOSE/OPEN
on
Mains operation
Mains voltage and frequency OK
MCB Opens On = GENRUN
None
Mains operation
EmergStart Del elapsed
MCB Opens On = MAINSFAIL
Engine start sequence
performed, then
GCB CLOSE/OPEN on
2
Island operation
EmergStart Del elapsed
MCB Opens On = GENRUN
Engine start sequence
performed, then MCB
CLOSE/OPEN off, time
delay Transfer Del
performed and GCB
CLOSE/OPEN on
2
Island operation
Island
operation
Mains voltage and frequency OK
MainsReturnDel timer
started
Mains return
Mains
return
Mains failed
Island operation
MainsReturnDel elapsed
GCB CLOSE/OPEN off,
then after Transfer Del
MCB CLOSE/OPEN on
and then engine stop
sequence performed
3
Mains operation
1
Mains failed means mains over/under -voltage, over/under -frequency, voltage assymetry (preset
delay must elapse)