InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp – January 2016 33
AMF26-P-2.4 Reference Guide.pdf
- Check ground connection from pick-up to controllers, eventually disconnect ground connection
to one of them
- Galvanically separate IL-NT RPM input using ComAp separation transformer RPM-ISO (1:1)
- Use separate pick-up for Speed governor and InteliLite
NT
Hint:
In some cases the controller will measure a RPM value even though the gen-set is not running:
RPM is measured from the generator voltage (Gear Teeth = 0)
IL-NT is measuring some voltage value on input terminals due to open fusing.
If RPM > 0 the controller will be put into a Not ready state and the engine will not be allowed to start.
Current measurement
To ensure proper function
Use cables of 2,5mm
2
Use transformers to 5A
Number Of CTs = 3CTs
Connect CT according to following drawings
Number Of CTs = 1CT
Connect CT according to following drawings. Terminals L2l and L3l are opened.