InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp January 2016 19
AMF26-P-2.4 Reference Guide.pdf
If IGL-RA15 remote announciator is not communicating with a controller via CAN bus, it activates a
warning.
See the documentation of RA15 for the technical and function description.
165 (6,5”)
38 (1,5)
40 (1,6)
~ 75 (3,0)
~ 35 (1,4)
180 (7,1”)
185 (7,3”)
106 (4,2)
44 (1,7”)
54 (2,1”)
~ 25 (1,0)
120 (4,7)
125 (4,9)
Cutout
for Remote Announciator
167 x 108 mm
(6,6 x 4,3 )
IG-IOM/PTM module
IG-IOM and IGS-PTM modules are I/O extension modules equipped with 8 binary inputs, 8 binary
outputs, 4 analog inputs and one analog output. The module can be used for AMF25, MRS15, 16, 19
only.
Binary inputs and outputs are configurable the same way like inputs and outputs on iL.
Analog inputs are configurable like iL with the limitation that the binary and tristate mode can
not be used on PTM module.
The protection of analog IOM/PTM inputs is activated by overcrossing the limits, active only
when the engine is running.
IG-IOM analog inputs are resistive (the same parameters like IL-NT) 0 :-2,4 k:. The module
IOM is designed for especially VDO resistive sensors.
IGS-PTM analog inputs are configurable by jumpers to ranges 0-250:, 0-100mV, 0-20mA.
The module can be used especially for Pt100 sensors and current sensors. The module PTM
is not suitable for VDO temperature sensor.
Hint:
- For a description of setting IGS-PTM module with current/voltage sensors please see the Extension
modules manual.
- When module is not configured by LiteEdit SW, controller does not show related values and