InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp January 2016 93
AMF26-P-2.4 Reference Guide.pdf
Hint:
IG-IOM/IGS-PTM analog inputs protection alarms can be configured following way.
Configuration
Protection
Under
Protection is activated only when measured value is under measured level.
Over
Protection is activated only when measured value is over measured level.
Under+fls
Level 2 protection is activated by Sensor Fail as well.
Over+fls
Level 2 protection is activated by Sensor Fail as well.
IOM AI1..4 Calibr […]
Calibrating constant to adjust the measured value of IOM/PTM analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Step: 1
Range: -1000 +1000
SMS/E-Mail
Remote alarm messaging
If a GSM modem and/or Internet bridge is connected to the controller, the controller can send SMS
messages and/or emails in the moment when a new alarm appears in the Alarm list. The message will
contain a copy of the Alarm list.
To enable this function, you should select with setpoints Yel Alarm Msg, Red Alarm Msg or Event
Msg, which levels of alarms shall be announced (red/yellow/both) and also enter valid GSM phone
number and/or e-mail address to the setpoints TelNo/Addr Ch1-2 and TelNo/Addr Ch3-4. It is possible
to put either a GSM* number or e-mail* to both setpoints.
There is also possibility to control the unit (e.g. read and/or write setpoints, send commands, etc.)
using sms messages. For more details about this function see SMS Message Control and
SMS/Email: Report Period setpoint description.
*The list of all supported terminals shows the table below:
Terminal
Active alarm
sms
Active event
sms
Active alarm
email
Active event
email
IB-Lite
N/A
N/A
YES
YES
IB-NT
N/A
N/A
YES/Ethernet
YES/Ethernet
IL-NT-GPRS
YES
YES
Not
supported
Not
supported
NOTE:
An internet module must be available for sending of e-mails. Similarly, a GSM modem is necessary for
sending of SMS.
Hint:
Controller will display ActiveCallFailxCH after 100s after last attempt.
Yel Alarm Msg [DISABLED / ENABLED]
Set this setpoint to YES if you want to get messages when a yellow (warning) alarm occurs.
Hint
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1-4