EasyManua.ls Logo

ComAp InteliLite NT AMF26-P - Remote Communication; Internet Connection; SMS Message Control

ComAp InteliLite NT AMF26-P
167 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp January 2016 142
AMF26-P-2.4 Reference Guide.pdf
Remote Communication
Hint:
Refer to InteliCommunication guide for all additional information.
Internet connection
IL-NT controllers can be monitored from LiteEdit over the Internet using Internet Bridge (IB-Lite),
pluged into the controller communication slot.
It is also possible to use IG-IB (connected to controller RS232 port) if needed.
SMS Message Control
You can control and setup the Genset using SMS messages from your mobile phone.
Please see also additional information about SMS messages in Report Period description.
SMS message format
SMS message format:
x Start with # character, followed controller address, followed colon character and access code,
x Commands are comma separated,
x Commands are not case sensitive,
x Maximum message length is limited up to 160 characters,
x Controller or I-LB answers only message with valid Access code,
x Answer exceeds 160 characters is separated to more messages.
SMS message header
Every SMS must start with header in format:
#address:access command1, command2
where address is controller address 1 to 32
access is valid access code set-up by PC SW (up to 15 characters length),
# character indicates beginning of message,
: character separates controller address and access code
Hint:
For direct communication to one controller is possible skip address setting.
SMS message commands
1. Controller address
Controller address is unique controller identification number located in setpoint group Basic
Settings : Contr addr [1 to 32].
Syntax: #XX
XX … controller address [1 to 32]
Example: #5
Message is addressed to controller with address 5.