InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp – January 2016 115
AMF26-P-2.4 Reference Guide.pdf
Relation between GCB and MCB (Test mode)
Situation 1: Mains =OK, MCB = closed, GCB = opened, RPM=0.
Change mode to TEST: gen-set starts, GCB = opened.
Mains cut: MCB opens (according 1.) , GCB closes (Transfer Del)
Situation 2: ReturnFromTEST=MANUAL, Mains =OK, MCB is closed, gen-set is running.
Press MCB on/off -> MCB opens, GCB closes (Transfer Del), gen-set is running loaded.
MCB opened
GCB closed
Fwd Return Del