InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp January 2016 122
AMF26-P-2.4 Reference Guide.pdf
Events
specification
Protection
type
Information on binary
output available (See
list of Binary outputs)
Description
Low BackupBatt
WRN
NO
RTC backup battery is flat
WrnMaintenance
WRN
YES
The period for servicing is set by the
Maintenance setpoint. The protection
comes active if the running hours of the
engine reach this value.
Wrn EFProtTest
WRN
NO
a) Binary output EF PROT TEST is active
(all the time even when performed EF Prot
Test is acknowledged by FAULT RESET)
b) Activated when EF Prot Test is
performed using ENTER + FAULT RESET
button’s combination or by EFProtTest
command in Man Operations group.
Sd GAutDtcFail
SD
NO
Gen-set autodetection failed = suitable
configuration not found in Alternate Cfg
group.
MAutDetecFail
WRN
NO
Mains autodetection failed = suitable
configuration not found in Alternate Cfg
group.
AlterCfg 1..3 Act
Successful autodetection.
(chosen configuration group indication)
*Only when ECU is configured