EasyManua.ls Logo

ComAp InteliLite NT AMF26-P - Page 137

ComAp InteliLite NT AMF26-P
167 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp January 2016 137
AMF26-P-2.4 Reference Guide.pdf
Gener Protect
EF Protection
ENABLED
Yes
11631
String list
Gener Protect
EarthFault Sd
0,30
A
No
11632
0,03
5,00
Unsigned 16
Gener Protect
EarthFault Del
0,10
s
No
11633
0,03
5,00
Unsigned 16
Gener Protect
Gen >V Sd
110
%
Yes
8291
80
200
Unsigned 16
Gener Protect
Gen <V BOC
80
%
Yes
8293
0
110
Unsigned 16
Gener Protect
Gen V Del
3,0
s
Yes
8292
0,0
600,0
Unsigned 16
Gener Protect
Volt Unbal Sd
10
%
Yes
8288
1
200
Unsigned 16
Gener Protect
Volt Unbal Del
3,0
s
Yes
8289
0,0
600,0
Unsigned 16
Gener Protect
Gen >Freq Sd
110,0
%
Yes
8296
90,0
200,0
Unsigned 16
Gener Protect
Gen <Freq BOC
90,0
%
Yes
8298
0,0
110,0
Unsigned 16
Gener Protect
Gen Freq Del
3,0
s
Yes
8297
0,0
600,0
Unsigned 16
AMF Settings
RetFromIsland
AUTO
Yes
9590
String list
AMF Settings
EmergStart Del
2
s
Yes
8301
0
6000
Unsigned 16
AMF Settings
MainsReturnDel
60
s
Yes
8302
1
3600
Unsigned 16
AMF Settings
MFB MReturnDel
60
s
Yes
12078
1
3600
Unsigned 16
AMF Settings
Transfer Del
1,0
s
Yes
8303
0,0
600,0
Unsigned 16
AMF Settings
MCB Close Del
1,0
s
Yes
8389
0,0
60,0
Unsigned 16
AMF Settings
MShortCrct
875,0
A
Yes
11626
1,0
1000,0
Unsigned 16
AMF Settings
MShortCrct Del
0,00
s
Yes
11627
0,00
10,00
Unsigned 16
AMF Settings
Mains >V
110
%
Yes
8305
80
150
Unsigned 16
AMF Settings
Mains <V
80
%
Yes
8307
50
110
Unsigned 16
AMF Settings
Mains V Del
2,0
s
Yes
8306
0,0
600,0
Unsigned 16
AMF Settings
Mains V Unbal
10
%
Yes
8446
1
150
Unsigned 16
AMF Settings
Mains VUnb Del
2,0
s
Yes
8447
0,0
60,0
Unsigned 16
AMF Settings
Mains >Freq
110,0
%
Yes
8310
90,0
150,0
Unsigned 16
AMF Settings
Mains <Freq
90,0
%
Yes
8312
50,0
110,0
Unsigned 16
AMF Settings
Mains Freq Del
0,5
s
Yes
8311
0,0
60,0
Unsigned 16
AMF Settings
MCB Logic
CLOSE-OFF
Yes
8444
String list
AMF Settings
ReturnFromTEST
MANUAL
Yes
8618
String list
AMF Settings
MCB Opens On
MAINSFAIL
Yes
9850
String list
Extension I/O
IOM AI1 Wrn
0
U4
No
8762
-100
10000
Integer 16
Extension I/O
IOM AI1 Sd
0
U4
No
8766
-100
10000
Integer 16
Extension I/O
IOM AI1 Del
5
s
No
8770
0
900
Unsigned 16
Extension I/O
IOM AI2 Wrn
0
U5
No
8763
-100
10000
Integer 16
Extension I/O
IOM AI2 Sd
0
U5
No
8767
-100
10000
Integer 16
Extension I/O
IOM AI2 Del
5
s
No
8771
0
900
Unsigned 16
Extension I/O
IOM AI3 Wrn
0
U6
No
8764
-100
10000
Integer 16
Extension I/O
IOM AI3 Sd
0
U6
No
8768
-100
10000
Integer 16

Table of Contents