InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp January 2016 79
AMF26-P-2.4 Reference Guide.pdf
Comparator OFF [ ]
Resolution = 1
OFF limit - once this limit is reached the Comparator output is switched off.
ComparatorFunc [list of functions bellow]
It will be possible to choose from the list of following logical functions, which may be activated at the
same moment when ON limit is reached and the Comparator output is activated.
List of functions:
No Func, Rem S/S, Rem Start, Rem Stop, EmergStop, Sd Ovrrd, Rem OFF, Rem MAN, Rem AUT,
Rem TEST, Rem T OnLd, Emerg Man
Note:
If the same function is already configured on binary input or as function of timer, it will be in logical OR
with the comparator function.
EMR2Preheating [ENABLED / DISABLED]
ENABLED: Should be used when Deutz EMR2 ECU is used and preheating function in its
configuration is activated.
DISABLED: Should be used when conditions above are not fulfilled, what means for all the other
ECU types, for mechanical engines and also for Deutz EMR2 when preheating
function in its configuration is NOT activated.
For more information about this function see also PREHEATING binary input description.
Dummy Ld 1 ON [A]
Limit for Dummy Load 1 activation.
Step: 1 A
Range: 1 10000 A
Dummy Ld 1 OFF [A]
Limit for Dummy Load 1 deactivation.
Step: 1 A
Range: 1 10000 A
Dummy Ld 2 ON [A]
Limit for Dummy Load 2 activation.
Step: 1 A
Range: 1 10000 A
Dummy Ld 2 OFF [A]
Limit for Dummy Load 2 deactivation.
Step: 1 A
Range: 1 10000 A
Dummy Load [GCB, MCB, GCB or MCB, ReadyToLd]
Common parameter determining when the Dummy Load function/output is active; either when only
GCB is closed (default setting) or when only MCB is closed or when either GCB or MCB is closed or in
case gen-set is in Ready To Load state ( = Ready To Load output is active).
Evaluation of this function is based on L1 current value. There is fixed 15 seconds delay for function
activation after Dummy Load parameter conditions are fulfilled (GCB and/or MCB closing and
switching to Ready To Load state). Once the function is activated (after 15 seconds delay) Dummy
Load ON/OFF limits are evaluated immediately without any delay.