InteliLite
NT
AMF26-P, SW version 2.4, ©ComAp – January 2016 99
AMF26-P-2.4 Reference Guide.pdf
controller front face panel or using Direct connection between controller and LiteEdit by double pressing
Fault Reset.Counter is active only, when the genset is running.
Step: 1h
Range: 0 –9999h
ServBasicDay [day]
It counts down when engine running. If reaches zero, an alarm appears. When the value 9999 is set, than
the maintenance function is disabled and counter does not count. . Alarm can be acknowledged from
controller front face panel or using Direct connection between controller and LiteEdit by double pressing
Fault Reset.
Step: 24h
Range: 0 –9999day
ServiceLvl2-8H [h]
It counts down when engine running. If reaches zero, an alarm appears. When the value 9999 is set, than
the maintenance function is disabled and counter does not count. . Alarm can be acknowledged from
controller front face panel or using Direct connection between controller and LiteEdit by double pressing
Fault Reset.
Counter is active only, when the genset is running.
Step: 1h
Range: 0 –9999h
ServLvl2-8Day [day]
It counts down when engine running. If reaches zero, an alarm appears. When the value 9999 is set, than
the maintenance function is disabled and counter does not count. . Alarm can be acknowledged from
controller front face panel or using Direct connection between controller and LiteEdit by double pressing
Fault Reset.
Step: 24h
Range: 0 –9999day
ServLvlOVH1H [h]
It counts down when engine running. If reaches zero, an alarm appears. When the value 9999 is set, than
the maintenance function is disabled and counter does not count. . Alarm can be acknowledged from
controller front face panel or using Direct connection between controller and LiteEdit by double pressing
Fault Reset.
Counter is active only, when the genset is running.
Step: 1h
Range: 0 –9999h
ServLvlOVH1Day [day]
It counts down when engine running. If reaches zero, an alarm appears. When the value 9999 is set, than
the maintenance function is disabled and counter does not count. . Alarm can be acknowledged from
controller front face panel or using Direct connection between controller and LiteEdit by double pressing
Fault Reset.
Step: 24h
Range: 0 –9999day