44 Culligan® Smart Controller (GBE) for Softeners and Filters
44 Cat. No. 01021161
Progressive Flow Update
With Firmware version 2.0.9 and later, the Smart Controller can now update all units in the system. After the master is
programmed, Follow these instructions:
1. Run the First Time Setup on all remaining units. You can skip through until you get to multi-tank. Select
PROGRESS FLOW and set the SLAVE ID. Skip through the rest of FTS.
1. From the HOME scrren, press to view the main menu.
2. The screen displays the main menu. Press to select 2)MANUAL MODE.
3. Press to select PFLOW UPDATE. This will transfer the program-
ming to all other systems.
The additional settings needed on the slave units will be for accessories such as Aqua-Sensor and Smart Brine Tank
Probe. Service phone number, wireless remote, and modem settings are not transferred because in a multi-tank system
they are installed on the Master only.