Design Guide | iC7-Automation Air-cooled Enclosed Drives Control and Option Installation
11 Option slots for the inverter module: AA5, AA6, AA7 =
option boards. Option slot for the AFE module: AB1 = I/O
and Relay Option OC7C1.
12 Options slots for the AFE module: AB2 =control board, AB3
= option board
13 Options slot AB4 = star coupler board for AFE, AA8 = star
coupler board for inverter
14 Spring-type terminals, -XD2.1, -XD2.2, -XD2.3
15 Door device terminals, -XDJ 16 Reserved for option terminals, for example, option slot
AA3 terminals or insulation monitoring terminals (+IMIF)
7.4 Control Compartment Connections
Table 12: Control Compartment Connections
Terminal Function Connector type
X1 Ethernet port RJ45
X2 Ethernet port RJ45
X0 Ethernet port (used for the PC tool) RJ45 (Cabled to the door -XD3.1 ethernet terminal)
Micro SD microSD card Micro SD
X62 24 V DC supply 2 x 3 spring force connector 0.2–1.5 mm
2
X33 STO terminal 1 x 10 spring force connector 0.2–1.5 mm
2
OptionBus OptionBus (internal connection) Custom
X80 Fiber optic link to power unit or star coupler board LC-duplex
X9 Control panel terminal iX Industrial
RTC battery RTC battery BR1632 (battery type)
Table 13: STO Terminal Signals (X33, XD2.2)
Terminal on the
control board
Function Terminal block Description
41A
(1)
24V -XD2.2:41 + 24 V DC Output
41B
(1)
24V -XD2.2:41 + 24 V DC Output
42 S.INA+ -XD2.2:42 + Safe Input Channel A
43 S.INB+ -XD2.2:43 + Safe Input Channel B
44 S.FB+ -XD2.2:44 + STO Feedback
45A
(1)
GND -XD2.2:45 0 V/GND
45B
(1)
GND -XD2.2:45 0 V/GND
46 S.INA- -XD2.2:46 - Safe Input Channel A
47 S.INB- -XD2.2:47 - Safe Input Channel B
48 S.FB- -XD2.2:48 - STO Feedback
1) Terminals 41A, 41B, 45A, and 45B have double pins to make connections easier.