EasyManua.ls Logo

Danfoss iC7-Automation - Installing the Power Cables through the Top (+KCIT or +KDOT)

Danfoss iC7-Automation
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
2
3
4
e30bj514.11
Figure 26: Cabling of the Enclosed Drive
1 Motor cables 2 Mains cables
3 Grounding conductor 4 PE busbar
10. Release and lower the service table.
6.6.2 Installing the Power Cables through the Top (+KCIT or +KDOT)
Use these instructions with the options Top-entry +KCIT and +KDOT.
DANGER
ELECTRIC SHOCK
There are live components behind the touch protections. Lack of touch protections can cause death or serious
injury.
l After power cabling, reinstall all touch protections at their original places.
1. Strip the mains and motor cables.
2. Make openings for the cables in the grommets at the top of the cabinet.
This applies for IEC installations.
The grommets must be suited to the output diameter of the cable. The cable diameter is 25–65 mm (1–2.6 in).
3. Lead the power cables through the grommet holders.
4. Peel the cable shield and attach the end to the PE busbar.
5. Use cable clamps to fix the cables.
6. To make a 360° connection, expose the shield of the cables. Use a cable tie to attach the knitted metal mesh tube.
44 | Danfoss Drives Oy © 2024.09 AJ389643274589en-000101 / 172F6409A
Design Guide | iC7-Automation Air-cooled Enclosed Drives Electrical Installation

Table of Contents

Related product manuals