EasyManua.ls Logo

Danfoss iC7-Automation - Motor Cable Size Recommendations, 380-500

Danfoss iC7-Automation
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Design Guide | iC7-Automation Air-cooled Enclosed Drives Specifications
3) Use bimetallic lugs. No direct aluminum contact to the mains terminals.
4) If the option Top-entry +KCIT is used, the maximum number of mains cables is 4.
5) If the option Top-entry +KCIT is used, the hole size is 13 mm.
9.5.3 Motor Cable Size Recommendations, 380–500 V
Table 41: Motor Cable Size Recommendations, 380–500 V
Model
code
Frame I
N
[A]
Cable [mm
2
]
Maximum
cable size
[mm
2
]
(1)
Maximum
number
of motor
cables
Bolt size
(2)
Number of
grounding
holes on PE
busbar
Hole size
of the
grounding
terminal
[mm]
iC7-60EA3N
05-206A
206 Cu 1 x (3x70+35)
Al 1 x (3x120+41
Cu)
95 Cu/Al
(3)
2
(4)
M10 2 Ø10.5
iC7-60EA3N
05-245A
245 Cu 1 x (3x95+50)
Al 1 x (3x150+41
Cu)
95 Cu/Al
(3)
2
(4)
M10 2 Ø10.5
iC7-60EA3N
05-302A
302 Cu 1 x (3x120+70)
Al 2 x (3x95+29 Cu)
95 Cu/Al
(3)
2
(4)
M10 2 Ø10.5
iC7-60EA3N
05-385A
FE9
385 Cu 2 x (3x95+50)
Al 2 x (3x120+41
Cu)
95 Cu/Al
(3)
2
(4)
M10 2 Ø10.5
iC7-60EA3N
05-480A
480 Cu 2 x (3x120+70)
Al 2 x (2x185+57
Cu)
150 Cu/120
Al
(3)
3
(4)
M10 4 Ø10.5
iC7-60EA3N
05-588A
FE10
588 Cu 2 x (3x150+70)
Al 2 x (3x240+41
Cu)
150 Cu/120
Al
(3)
3
(4)
M10 4 Ø10.5
iC7-60EA3A
05-385A
394 Cu 1 x (3x185+95)
Al 2 x (3x120+41
Cu)
240 Cu/Al
(3)
4
(4)
M10 4 Ø10.5
iC7-60EA3A
05-480A
490 Cu 2 x (3x120+70)
Al 2 x (3x150+70
Cu)
240 Cu/Al
(3)
4
(4)
M10 4 Ø10.5
iC7-60EA3A
05-590A
AE10 +
IE10
601 Cu 2 x (3x150+70)
Al 2 x (3x185+57
Cu)
240 Cu/Al
(3)
4
(4)
M10 4 Ø10.5
Danfoss Drives Oy © 2024.09 AJ389643274589en-000101 / 172F6409A | 111

Table of Contents

Related product manuals