Design Guide | iC7-Automation Air-cooled Enclosed Drives Specifications
3) Use bimetallic lugs. No direct aluminum contact to the mains terminals.
4) If the option Top-entry +KCIT is used, the maximum number of mains cables is 4.
5) If the option Top-entry +KCIT is used, the hole size is 13 mm.
9.5.3 Motor Cable Size Recommendations, 380–500 V
Table 41: Motor Cable Size Recommendations, 380–500 V
Model
code
Frame I
N
[A]
Cable [mm
2
]
Maximum
cable size
[mm
2
]
(1)
Maximum
number
of motor
cables
Bolt size
(2)
Number of
grounding
holes on PE
busbar
Hole size
of the
grounding
terminal
[mm]
iC7-60EA3N
05-206A
206 Cu 1 x (3x70+35)
Al 1 x (3x120+41
Cu)
95 Cu/Al
(3)
2
(4)
M10 2 Ø10.5
iC7-60EA3N
05-245A
245 Cu 1 x (3x95+50)
Al 1 x (3x150+41
Cu)
95 Cu/Al
(3)
2
(4)
M10 2 Ø10.5
iC7-60EA3N
05-302A
302 Cu 1 x (3x120+70)
Al 2 x (3x95+29 Cu)
95 Cu/Al
(3)
2
(4)
M10 2 Ø10.5
iC7-60EA3N
05-385A
FE9
385 Cu 2 x (3x95+50)
Al 2 x (3x120+41
Cu)
95 Cu/Al
(3)
2
(4)
M10 2 Ø10.5
iC7-60EA3N
05-480A
480 Cu 2 x (3x120+70)
Al 2 x (2x185+57
Cu)
150 Cu/120
Al
(3)
3
(4)
M10 4 Ø10.5
iC7-60EA3N
05-588A
FE10
588 Cu 2 x (3x150+70)
Al 2 x (3x240+41
Cu)
150 Cu/120
Al
(3)
3
(4)
M10 4 Ø10.5
iC7-60EA3A
05-385A
394 Cu 1 x (3x185+95)
Al 2 x (3x120+41
Cu)
240 Cu/Al
(3)
4
(4)
M10 4 Ø10.5
iC7-60EA3A
05-480A
490 Cu 2 x (3x120+70)
Al 2 x (3x150+70
Cu)
240 Cu/Al
(3)
4
(4)
M10 4 Ø10.5
iC7-60EA3A
05-590A
AE10 +
IE10
601 Cu 2 x (3x150+70)
Al 2 x (3x185+57
Cu)
240 Cu/Al
(3)
4
(4)
M10 4 Ø10.5
Danfoss Drives Oy © 2024.09 AJ389643274589en-000101 / 172F6409A | 111