Danfoss iC7-Automation - Installing the Back-Channel Cooling Option

Danfoss iC7-Automation
132 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
e30bj468.11
1
1
2
2
Figure 17: Cooling Air Output Flange (+OAOF), Intake Front or Back, Output Top
1 Air intake at the back 2 Air intake in the front
Table 9: Number of Air Output Holes in the Cooling Air Output Flange
Width of the cabinet [mm (in)] Number of holes at the top
400 (15.7) 1
600 (23.6) 2
800 (31.5) 3
See the dimensions of the cooling options:
l
9.2.7 Dimensions for Back-channel Cooling Option, FE9
l 9.2.8 Dimensions for Back-channel Cooling Option, FE10
l 9.2.9 Dimensions for Back-channel Cooling Option, AE10, AE11, IE10, IE11
l 9.2.10 Dimensions for the Cooling Air Output Flange Option, FE9
l 9.2.11 Dimensions for the Cooling Air Output Flange Option, FE10
l 9.2.12 Dimensions for the Cooling Air Output Flange Option, AE10, AE11, IE10, IE11
5.7 Installing the Back-channel Cooling Option
1. Attach the cover plate of the top hood with 4 screws.
36 | Danfoss Drives Oy © 2024.09 AJ389643274589en-000101 / 172F6409A
Design Guide | iC7-Automation Air-cooled Enclosed Drives Mechanical Installation