Example 1
Illustration 11: Example Installation 1
Table 11: Cabinet Data for Installation Example 1
This installation applies to drive types:
NXP1150 5
NXP0920 6
NXP1030 6
NXP1180 6
Minimum required cabinet width:
600 mm (Cabinet A) + 800 mm (Cabinet B)
(23.62 in (Cabinet A) + 31.50 in (Cabinet B))
Minimum required cabinet height:
Required weight carrying capacity:
NXP1150 5: 480 kg (1058.2 lb) (Cab. A); 540 kg (1190.5 lb) (Cab. B)
NXP0920 6: 450 kg (992.1 lb) (Cab. A); 540 kg (1190.5 lb) (Cab. B)
NXP1030 6: 450 kg (992.1 lb) (Cab. A); 540 kg (1190.5 lb) (Cab. B)
NXP1180 6: 480 kg (1058.2 lb) (Cab. A); 540 kg (1190.5 lb) (Cab. B)
This manual applies to IP21.
See 5.2.1 Ventilation of the Cabinet.