Example 2
A1
U V W
dUdt
PE
A B
1
2 2 2
4
1 1
3
5 5
e30bj126.10
Illustration 12: Example Installation 2
Table 12: Cabinet Data for Installation Example 2
This installation applies to drive types:
NXP1300 5 (6-pulse)
NXP1450 5 (6-pulse)
Minimum required cabinet width:
800 mm (Cab. A) + 800 mm (Cab. B)
(31.50 in (Cab. A) + 31.50 in (Cab. B)
Minimum required cabinet height:
Required weight carrying capacity:
635 kg (1399.9 lb) (Cab. A); 590 kg (1300.7 lb) (Cab. B)
This manual applies to IP21.
See 5.2.1 Ventilation of the Cabinet.