Example 3
A1A1
dUdt
A B C
1
2 2 2 2
1 1 1
3
4
U V W
PE
5 5 5
e30bj125.10
Illustration 13: Example Installation 3
Table 13: Cabinet Data for Installation Example 3
This installation applies to drive types:
NXP1300 5 (12-pulse)
NXP1450 5 (12-pulse)
Minimum required cabinet width:
600 mm (Cab. A) + 800 mm (Cab. B) + 600 mm (Cab. C)
(23.62 in (Cab. A) + 31.50 in (Cab. B) + 23.62 in (Cab. C))
Minimum required cabinet height:
Required weight carrying capacity:
450 kg (992.08 lb) (Cab. A and C); 540 kg (1190.5 lb) (Cab. B)
This manual applies to IP21.
See 5.2.1 Ventilation of the Cabinet.