Operator info Additional information
Available power too
low
There is an overload present on the
busbar the genset is connecting to.
Cancelling the Close breaker command
will cause a blackout.
Blackout start block
activated
The Block blackout start function is active.
Blackout start block
deactivated
The Block blackout start function is not
active.
Breaker already
closed
The breaker is already closed and cannot
be closed again.
Breaker already
opened
The breaker is already open and cannot
be opened again.
BTB block not
possible in SWBD
While the controller is under switchboard
controller, operator actions cannot be
performed from the controller interfaces.
BTB close blocked
The Block bus tie breaker close function is
active. A closed breaker will not open
automatically, and an open breaker cannot
be closed.
BTB close cancelled
The closing of Bus tie breaker has been
cancelled.
BTB close not
possible in SWBD
While the controller is under switchboard
controller, operator actions cannot be
performed from the controller interfaces.
BTB close unblocked
The Block bus tie breaker close function is
not active.
BTB open cancelled
The opening of Bus tie breaker has been
cancelled.
BTB open not possible
in SWBD
While the controller is under switchboard
controller, operator actions cannot be
performed from the controller interfaces.
Busbar A voltage/
frequency not OK
The bus tie breaker cannot connect to a
dead or unknown state busbar. The bus
tie breaker will not close until busbar state
is OK and known.
Busbar B voltage/
frequency not OK
The bus tie breaker cannot connect to a
dead or unknown state busbar. The bus
tie breaker will not close until busbar state
is OK and known.
Busbar V/Hz not OK
The shaft generator cannot be connected
to a dead or unknown state busbar while it
is in power take home mode. The shaft
generator breaker will not close until
busbar state is OK and known.
Engine already
running
The engine is already running and cannot
be started again.
Engine already
stopped
The engine has already stopped and
cannot be stopped again.