Operator info Additional information
Engine block not
possible in SWBD
While the controller is under switchboard
controller, operator actions cannot be
performed from the controller interfaces.
● ●
Engine is stopping
The command has already been received.
The controller is executing the engine stop
procedure.
● ●
Engine not ready
The genset cannot start. There might be
alarms blocking the ready status.
● ●
Engine start and
breaker close not
possible in SWBD
While the controller is under switchboard
controller, operator actions cannot be
performed from the controller interfaces.
●
Engine start blocked
The Block engine start function is active. A
running genset will not stop, and a
stopped genset cannot be started.
● ●
Engine start not
possible in SWBD
While the controller is under switchboard
controller, operator actions cannot be
performed from the controller interfaces.
● ●
Engine start
unblocked
The Block engine start function is not
active.
● ●
Engine stop not
possible in SWBD
While the controller is under switchboard
controller, operator actions cannot be
performed from the controller interfaces.
● ●
Force all in section to
AUTO mode activated
The Force all controllers in section to
AUTO mode function is active.
● ● ● ● ●
Force all in section to
SEMI mode activated
The Force all controllers in section to
SEMI mode function is active.
● ● ● ● ●
Force all in section to
SWBD control
activated
The Force all controllers in section to
SWBD control function is active.
● ● ● ● ●
Force all in section to
SWBD control
deactivated
The Force all controllers in section to
SEMI mode function is not active.
● ● ● ● ●
GB block not possible
in SWBD
While the controller is under switchboard
controller, operator actions cannot be
performed from the controller interfaces.
● ●
GB close blocked
The Block generator breaker close
function is active. A closed breaker will not
open automatically, and an open breaker
cannot be closed.
● ●
GB close cancelled - ● ●
GB close not possible
in SWBD
While the controller is under switchboard
controller, operator actions cannot be
performed from the controller interfaces.
●
GB close unblocked
The Block generator breaker close
function is not active.
● ●
GB is closed The Generator breaker is closed. ● ●
GB is de-loading
The Generator breaker is currently de-
loading.
● ●
PPM 300 Operator's manual 4189340910 UK