70 of 152 PSS5000/TEMA/803046/05
PSS 5000 – Technical Manual
6 Operation (Menu 3)
Manual report creation A check box and Enable/Disable button that al-
low you to activate/deactivate the Create Report
button.
Note: Both the check box and the button must
be used to change the state of the Create Report
button.
Totalizer Readings (liter)
Fuelling Point n Each fuelling point has 3 values:
• Start – this value is provided by the previous
Site report.
• End – this values is provided by the current
Site report.
• Metered Sale – this is a calculated value:
(End value – Start value)
Note: Depending on the type of pump, the Start
and End values can be either measured values
from the pump or calculated values from trans-
action data.
Total Sale This is a summation of Metered Sale values for
all the fuelling points connected to the tank.
ATG Readings (liter)
Gauged Volume: Start This is measured value from the tank gauge
system when the previous site report was creat-
ed.
Delivered This is measured value provided by tank gauge
system, which states the amount of any deliver-
ies made after the Start and before the End val-
ues were provided.
Gauged Volume: End This is measured value from the tank gauge
system when the current site report was creat-
ed.
Tank Gauge Sale This is a calculated value:
(End – Start) + Delivered
Reconciliations
Tank Group This is a tank group ID. It is only relevant when
multiple tanks are manifolded.
Dif. (liters) This is a calculated value (for each tank), which
compares the values supplied by the 2 sources:
Dif. (%) This is a calculated value (for each tank) which
compares the values supplied by the 2 sources:
Parameter Description
Total Totalizer Sale Total Tank Gauge Sale–
Total Totalizer Sale Total Tank Gauge Sale–()100×
Total Totalizer Sale
-------------------------------------------------------------------------------------------------------------------------------