8 Appendix
8.3 Technical data
214 Operating instructions 05/10 MN05013003Z-EN www.eaton.com
8.3.4.2 EASY-512-AC-…, EASY618-AC-.E, EASY719-AC-…
EASY-512-AC-… EASY618-AC-.E, EASY719-AC-...
Digital inputs 115/230 V AC
Number 8 12
Status display LCD (if provided) LCD (if provided)
Potential isolation
From power supply No No
between digital inputs No No
from the outputs Yes Yes
Rated voltage L (sinusoidal)
At signal “0” 0 - 40 V AC 0 - 40 V AC
At signal ”1”
79 - 264 V AC 79 - 264 V AC
Rated frequency
50/60 Hz 50/60 Hz
Input current with "1" signal
R1 to R12, I1 to I6
(EASY71. also I9 to I12)
6 x 0.5 mA at 230 V AC 50 Hz,
6 x 0.25 mA at 115 V AC 60 Hz
10 x (12) 0.5 mA at
230 V AC, 50 Hz
10 x (12) x 0.25 mA at
115 V AC, 60 Hz
Input current on signal 1
I7, I8
2 x 6 mA at 230 V AC 50 Hz,
2 x 4 mA at 115 V AC 60 Hz
2 x 6 mA at 230 V AC 50 Hz,
2 x 4 mA at 115 V AC 60 Hz
Delay time for 0 to 1 and 1 to 0 for I1 to I6, I9 to I12
Debounce ON
80 ms (50 Hz), 66²/3 ms (60 Hz) 80 ms (50 Hz), 66²/3 ms (60 Hz)
Debounce OFF
(also R1 to R12)
20 ms (50 Hz), 16²/3 ms (60 Hz) 20 ms (50 Hz), 16²/3 ms (60 Hz)
Delay time I7, I8 for 1 to 0
Debounce ON
160 ms (50 Hz), 150 ms (60 Hz) 80 ms (50 Hz),66²/3 ms (60 Hz)
Debounce OFF 100 ms (50 Hz/60 Hz) 20 ms (50 Hz), 16²/3 ms (60 Hz)
Delay time I7, I8 for 0 to 1
Debounce ON
80 ms (50 Hz), 66²/3 ms (60 Hz) 80 ms (50 Hz), 66²/3 ms (60 Hz)
Debounce OFF 20 ms (50 Hz), 16²/3 ms (60 Hz) 20 ms (50 Hz), 16²/3 ms (60 Hz)
Max. permissible cable length (per input)
I1 to I6, R1 to R12
(at EASY719-.. also I9 to
I12)
Normally 40 m Normally 40 m
I7, I8
Normally 100 m Normally 100 m