7 Pilot devices M22-SWD…
7.3 M22-SWD base fixing
SmartWire-DT module IP20 01/20 MN05006001Z-EN www.eaton.com 191
One SmartWire-DT function element is used per slot. Correspondingly more
efficient function elements are used for the combined function of a luminous
command device or for the realization of a multi-step switch.
A luminous pushbutton, which previously had to be realized as a combination
of several elements, can now be realized simply by means of one combina-
tion element (LED indicator + contact element = M22-SWD-K11LEDC).
M22-SWD-KC11
This function element replaces the previous contact elements M22-KC10/
KC01. It provides a changeover contact by means of which both a breaker
and maker function can be realized. The function element is used in combina-
tion with M22 (pushbutton) actuators.
M22-SWD-KC22
This function element replaces multiple combinations of the previous contact
elements M22-KC10/KC01. It provides two changeover contacts, by means
of which control switches can be operator controlled with up to three-posi-
tion indication.
M22-SWD-LEDC…
This function element is used in combination with the indicator lights M22-
L.... White, blue, green or red are available as colours.
M22-SWD-K11LEDC… (multiple function elements)
→
Non-used slots have to be equipped with the SmartWire-DT
bridge M22-SWD-SEL8-10, otherwise the SmartWire-DT net-
work will be interrupted.
→
The PCBs contain a switchable terminating resistor for the
SmartWire-DT network. If the surface mounting enclosure is the
last slave in the network, the terminating resistor must be
switched on.
→
You can also obtain information about terminating resistors and
on the use of the SWD link via the software program SWD-
Assist.
http://www.eaton.eu/software
→
Further M22-KC10-/KC01 contact elements can be installed
here in the free locations in the surface mounting enclosure.
A possible application is, for example, conventional switching
via an M22-K... contact element and the reporting of this pro-
cess to the PLC via the M22-SWD-K11 function element.
→
Further M22-KC... contact elements can be installed here in the
free locations in the surface mounting enclosure.