Menu2-1-4Zone2AAltern.
COOLING 2A POS: XXXXX Entry Default
Setpoint R2.3 XXX °C Supply air temperature setpoint -10..20 0 °C
Hystersis R2.3 X K Supply air temperature hysteresis setpoint 1..8 4 K
Setpoint R4.3 XXX °C Return air temperature setpoint for comparison -10..25 5 °C
Hystersis R4.3 X K Return air temperature hysteresis setpoint 1..8 2 K
Menu2-2Defrost
DEFROST POS: XXXXX
1 Zone 1 Menu 2-2-1
2 Zone 2 Menu 2-2-2
Only shown when two-zone operation is set (Menu 6-1)
3 Zone 1A Altern. Menu 2-2-3
Not shown when setpoint toggle is disabled (Menu 3-3)
4 Zone 2A Altern. Menu 2-2-4
Only shown when two-zone operation is set (Menu 6-1) and setpoint toggle is not
disabled (Menu 3-3)
Menu2-2-1Zone1
DEFROST 1 POS: XXXXX Entry Default
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 5..20 8 °C
M/S Degiv.Fct. XXX Configuration of the defrost via CAN bus function.
For details see chapter Master-Slave-Modus -
Abtau-Synchronisation über CAN-Bus.
OFF, MASTR, SLAVE OFF
M/S CAN Adr. XXX Selection of the controller (1..99) participating in
the defrost via CAN bus which is the master.
"--", if this controller is itself master (Parameter M/
S Degiv.Fct.. = MASTR)
---, 1..99
DS-Function XXX Configuration of the defrost sequence function
(DS).For details see chapter Folgeabtauung (FA)
über CAN-Bus.
OFF, MASTR, SLAVE OFF
DS-Group XXX Selection of which group a defrost sequence of
this controller (1..99) belongs to.
---, 1..99
DS-Master XXX Selection of which controller (1..99) participating
in the defrost sequence is the master.
"--", if this controller is itself the master(Parameter
DS-Function = MASTR)
---, 1..99
DS-Wait time XXXm Wait time for the defrost sequence 0..127 1 min
Menu2-2-2Zone2