9.1.7 Menu 6 Configuration UA 111
KONFIGURAT POS: XXXXX
1 Refrigeration point Continue to menu 6-1
2 Controller Continue to menu 6-2
3 Cooling Continue to menu 6-3
4 Language Continue to menu 6-4
5 Alarm Priorities Continue to menu 6-5
6 Emergency power operation Continue to menu 6-6
7 Advanced Continue to menu 6-7
Menu 6-1 - Refrigeration point
KÜHLSTELLE POS:
XXXXX
Input Default
Refr. Pt. Name: Only text
xxxxxxxxxxxxxxx Free text that designated the refrigeration point
(see note after the table)
Case controller
Position: XXXXX Free text that is displayed in the menu after
position (POS) (see note after the table)
UA400
Priority: XX Priority of the alarms for refrigeration point failure
or setting of the global controller priority (menu
6-5)
, , or numbers (0..99)
1
Verbund Nr.: XX Number of the pack controller that the case
controller is assigned to
, , or numbers (--,
1..9)
1
Verbundsatz: XXX Membership of a compressor pack;
This parameter is only required for coupling to a
VS 3010 BS with multiple zones. This parameter
must be disabled (--) if any other type of pack
controller is used.
, , or numbers (---, Z1,
Z2)
Temperaturzonen X Number of temperature zones
Single-zone operation
Two-zone operation
, , or numbers (1, 2)
2
Fühleranzahl XX Display of the connected temperature sensors
After input of , a sensor scan is performed,
during which the number of sensors is
determined again.
The priority for older versions of the store computer (< V5.0) may only be allocated in the range 0..2;
seechapter10.1 Alarm signalling and monitoring Alarm signalling / individual allocation of the priorities.