Firmware V3.15
21.04.2021
233/401
9.4.2 Menu 1 Actual Values UA 131 / UA 131 LS
ACT VALUES POS: XXXXX
1 Temp. Sensor Move to menu 1-1
2 Cooling Zone 1 Move to menu 1-2
3 Defrost Zone 1 Move to menu 1-3
4 Not used with this controller type
5 Alarm Move to menu 1-5
6 Frame Heater Move to menu 1-6
7 Cooling Zone 2 Move to menu 1-7
Only shown when two-zone operation is set (Menu 6-1)
8 Defrost Zone 2 Move to menu 1-8
Only shown when two-zone operation is set (Menu 6-1)
Menu1-1Temp.Sensor
TEMPERATUR Pos: XXXXX
Temp. R2.1 xxx °C Current supply air temperature Input Z11/ Z12
Temp. R4.1 xxx °C Current return air temperature Input Z21/ Z22
Temp. R1.1 xxx °C Current evaporator defrost termination temperature Input Z31/ Z32
Temp. R4.2 xxx °C Current return air temperature Input Z41/ Z42
Temp. R1.2 xxx °C Current evaporator defrost termination temperature Input Z51/ Z52
Temp. R2.3 xxx °C Current supply air temperature Input Z61/ Z62
Temp. R4.3 xxx °C Current return air temperature Input Z71/ Z72
Temp. R1.3 xxx °C Current evaporator defrost termination temperature Input Z81/ Z82
Temp. R4.4 xxx °C Current return air temperature Input Z91/ Z92
Temp. R1.4 xxx °C Current evaporator defrost termination temperature Input Z01/ Z02
Menu1-2CoolingZone1
COOLING 1 Pos: XXXXX
Cooling xxx Current ON/OFF status of cooling
Run Time xx % Cooling relay on time during last day (00:00 - 24:00 hours)
Starts 0 Cooling relay actuations during last day
Temp. R2.1 xxx °C Current supply air temperature Input Z11/Z12