EasyManua.ls Logo

ECKELMANN UA 400 - Basic Settings; Setting the CAN Bus Address

ECKELMANN UA 400
401 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware V3.15
21.04.2021
81/401
6.2 Basic settings
Settings BEFORE the connection of the power supply - S1, S2, S3
Decade switches S1 and S2:
-SettingoftheCANbusaddress(nodenumber)1..99,seechapterSetting the CAN bus address
DIP switch S3:
-Controllertypesetting
-Master/Slavemode
-Settingofspecialfunctions,seechapterSetting of the controller type and master/slave mode
Settings AFTER application of the power supply
Erstanlauf - Regler auf Werkseinstellungen zurücksetzen(optionalsettingtodefaultvaluestoreacha
defined initial state for a running operation)
Configurationofthecontroller,seechapterGrundkonfiguration des Reglers
6.2.1 Setting the CAN bus address
Setting of the CAN bus address (Kn.nnn = 1..99) is performed using the two decade switches S1 and S2. An
individual CAN bus address must first be set at the two decade switches on all case controllers that are
installed in refrigerated cases beforecommissioning.
Risk of confusion!Inordertoavoidmix-ups,itisrecommendedtousethepositionnumberofthe
refrigerated case as CAN bus address. A different CAN bus address that must be unique in this system
must be allocated to each refrigeration point. The CAN bus address is inactive if both decade switches
aresetto0(i.e.theaddressis00).Thecontrollerisnotrecognisedasabusnode.

Table of Contents

Related product manuals