Menu 2-5-3 Mode altern.
Selectbetweenvalues.Checkmarkshowscurrentsetting.
MODE ALT POS: XXXXX Entry Default
fixed run time
Fixed frame heater on time
enthalpy-ctrl rtm Enthalpy control by ambient air temperature and
humidity
Menu2-5-4Setpointaltern.
SOLLW. UM POS: XXXXX Entry Default
Mod: xxxxxxxxxxxx Displays set frame heater mode (Menu 2-5-3) Fixed on time
Run Time XXX % Fixed on time, Only shown when mode set to
Fixed On Time (Menu 2-5-3)
--, 0..100 100 %
emerg.run time XXX % On time in failure of ambient air humidity or
temperature signal (via CAN bus)
Only shown when mode set to Enthalpy Control
(Menu 2-5-3)
--, 0..100 100 %
enthalp. offs. XXX % Offset to on time with activated enthalpy control
(via CAN bus)
Only shown when mode set to Enthalpy Control
(Menu 2-5-3)
-50..50 0 %