Firmware V3.15
21.04.2021
183/401
DERF. TIMER POS: XXXXX Entry Default
Defr. 4 xxxxx hh:mm Defrost start time with internal defrosting;
Weekday, time; shown only when parameter
defrost timer = INT
, ,(Mo-Suetc.)or
numbers (hh:mm)
Mo-Su20:00
...
Defr. 14 xxxxx hh:mm
Menu3-2-aDef.Tim.Z2
DEFR.TIMER POS: XXXXX Entry Default
Defrost Timer XXX Setting for how temperature zone 2 should
defrost:- MitZ1 Together with zone 1- INT
Internally-EXTExternally–thedefrostofboth
temperature zones is started simultaneously via
the external signal
, ,
(ViaZ1(ViaZ1,EXT,INT)
ViatZ1
Safe Defr Time XXX m Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120 60 min
Manual Defrost XXX Status (ON/OFF) of auxiliary manual defrost *)
, ,(ON/OFF)
OFF
Defr. 1 xxxxx hh:mm Defrost start time for internal defrost; weekday,
time of day; shown only when parameter defrost
timer = INT
, ,(Mo-Su)ornumbers
(hh:mm)
Mo-Su01:00
...
Defr. 14 xxxxx hh:mm
*) Parameter automatically set to ON for safe defrost time at first start.