• Menu6-5Alarmpriorities
ALARMPRIOS POS: XXXXX
Entry Default
Prio.Refrig. Pt. X Global alarm priority by refrigeration point priority
(Menu 6-1) (Y)
, , (Y,N)
N
Priority: XX Show refrigeration point priority (Menu 6-1)
Only shown when refrigeration point priority set to
Y.
Following parameters are only
shown when refrigeration point
priority is set to N. Meaning of
usable entries for alarm
priority:-=Event ignored0=Message
(entered only in message log)
1=Priority 1 alarm..99=Priority 99
alarm
Low Temp. Temperature below lower alarm limit
Priority applies to following alarms:
Low Temp. Zone1, Low Temp. Zone2
-, 0..99 2
High Temp. Temperature above upper alarm limit
Priority applies to following alarms:
High Temp. Zone1, High Temp. Zone2
-, 0..99 1
Sensor Fault Temperature sensor failure
-, 0..99 2
No Defrost No defrost within alarm delay interval
Priority applies to following alarm: No defrost
-, 0..99 2
Timer-Term.Defr. Defrosting terminated by safe defrost time
-, 0..99 0
Power Failure Start following power failure
-, 0..99 0
First Start Controller start up (basic settings loaded!)
-, 0..99 2
Manual Shutoff Manual switch Input D31/D32 set OFF
-, 0..99
0
Hardware Fault Internal hardware fault
Priority applies to following alarms: EEPROM Fault,
RTC Fault, Flash Fault
-, 0..99 1
Setpoint Change Message generated on changing setpoint
-, 0..99 0
Refrig.Pt.Dis. Cooling by pack controller via CAN bus interrupted
-, 0..99 0
Battery Voltage Battery low
-, 0..99 0