Firmware V3.15
21.04.2021
215/401
Menu3-2-aDef.Tim.Z2
DEFR.TIMER POS: XXXXX Entry Default
Defrost Timer XXX Setting for how temperature zone 2 should
defrost:- MitZ1 Together with zone 1- INT
Internally-EXTExternally–thedefrostofboth
temperature zones is started simultaneously via
the external signal
, ,
(ViaZ1(ViaZ1,EXT,INT)
ViatZ1
Safe Defr Time XXX m Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..120 60 min
Manual Defrost XXX Status (ON/OFF) of auxiliary manual defrost *)
, ,(ON/OFF)
OFF
Defr. 1 xxxxx hh:mm Defrost start time for internal defrost; weekday,
time of day; shown only when parameter defrost
timer = INT
, ,(Mo-Su)ornumbers
(hh:mm)
Mo-Su 01:00
...
Defr. 14 xxxxx hh:mm
Menu3-3ToggleSetpoints
TOGGLE POS: XXXXX Entry Default
Status XXX Setpoint toggle status (OFF/ON) of alternative
set of setpoints (setpoint toggle)
Toggle Setp. XXX Setpoint toggle via
EXT digital input D21/22
INT internal timer
CANbus-„--"deactivated
, ,(EXT,INT,CAN,--)
EXT
Blind On Time X s Fan and cooling stop time after toggling to
alternative set of setpoints with external setpoint
toggle (Menu 3-3)
0..250 50 sec
Alt
ON: DD-DD hh:mm
Start time for toggle to alternative set of setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3)
, ,(Mo-Suetc.)or
numbers (hh:mm)
Mo-Su
21:00
Alt
OFF: DD-DD hh:mm
End time for toggle to alternative set of setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3
, ,(Mo-Suetc.)or
numbers (hh:mm)
Mo-Su
05:00
Alt
ON: DD-DD hh:mm
Start time for toggle to alternative set of setpoints
Weekday from - to XXXXX, time hh:mm
Only shown when internal setpoint toggle is
activated (Menu 3-3)
, ,(Mo-Suetc.)or
numbers (hh:mm)
Su
05:00
*) Parameter automatically set to ON for safe defrost time at first start.