Firmware V3.15
21.04.2021
224/401
Menu6-5Alarmpriorities
ALARMPRIOS POS: XXXXX Entry Default
Prio.Refrig. Pt. X Global alarm
priority by
refrigeration point
priority (Menu
6-1) (Y)
, , (Y,N)
N
Priority: XX Show
refrigeration point
priority (Menu
6-1)
Only shown when
refrigeration point
priority set to Y.
Following parameters are only shown when refrigeration
point priority is set to N. Meaning of usable entries for
alarm priority:-=Event ignored0=Message (entered only in
message log) 1=Priority 1 alarm..99=Priority 99 alarm
Low Temp. Temperature
below lower alarm
limit
Priority applies to
following alarms:
Low Temp.
Zone1, Low
Temp. Zone2
-, 0..99 2
High Temp. Temperature
above upper
alarm limit
Priority applies to
following alarms:
High Temp.
Zone1, High
Temp. Zone2
-, 0..99 1
Sensor Fault Temperature
sensor failure
-, 0..99 2
No Defrost No defrost within
alarm delay
interval
Priority applies to
following alarm:
No defrost
-, 0..99 2
Timer-Term.Defr. Defrosting
terminated by
safe defrost time
-, 0..99 0
Power Failure Start following
power failure
-, 0..99 0
First Start Controller start up
(basic settings
loaded!)
-, 0..99 2
Manual Shutoff Manual switch
Input D31/D32 set
OFF
-, 0..99 0