Menu2-2-3Zone1AAltern.
DEFROST 1A POS: XXXXX Entry Default
Counting Rate Counting rate 0..15 3
Defrost Counter Defrost counter - 1
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..20 10 °C
Wait Time xx m Waiting time setpoint between cooling and
defrosting
0 .. 15 3 m
Drip Time x m Waiting time (drain time) setpoint between
defrosting and cooling
0 .. 15 5 m
Menu2-2-4Zone2AAltern.
DEFROST 2A POS: XXXXX Entry Default
Counting Rate Counting rate 0..15 3
Defrost Counter Defrost counter - 1
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..20 10 °C
Wait Time xx m Waiting time setpoint between cooling and
defrosting
0 .. 15 3 m
Drip Time x m Waiting time (drain time) setpoint between
defrosting and cooling
0 .. 15 5 m
Menu 2-3
Not used with this controller type.
Menu2-4Alarm
ALARM POS: XXXXX
1 Zone 1 Menu 2-4-1
2 Zone 2 Menu 2-4-2
Only shown when two-zone operation is set (Menu 6-1)
3 Zone 1A Altern. Menu 2-4-3
Not shown when setpoint toggle is disabled (Menu 3-3)
4 Zone 2A Altern. Menu 2-4-4
Only shown when two-zone operation is set (Menu 6-1) and setpoint toggle is not
disabled (Menu 3-3)
Menu2-4-1Zone1
ALARM 1 POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-20..30 -12 °C
Low Temp Setp. XX K Low temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 4 K