Firmware V3.15
21.04.2021
272/401
Menu2-4-2Zone2
ALARM 2 POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-30..30 -12 °C
Low Temp Setp. XX K Low temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 4 K
Menu2-4-3Zone1AAltern.
ALARM 1A POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-30..30 -14 °C
Low Temp Setp. XX K Low temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 4 K
Menu2-4-4Zone2AAltern.
ALARM 2A POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-30..30 -14 °C
Low Temp Setp. XX K Low temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..6 4 K
Menu2-5FrameHeater
FRAME HTR POS: XXXXX
1 Mode altern. Move to menu 2-5-1
2 Setpoint frm htr Move to menu 2-5-2
3 Mode altern. Move to menu 2-5-3
Not shown when setpoint toggle is disabled (Menu 3-3)
4 Setpoint altern. Move to menu 2-5-4
Not shown when setpoint toggle is disabled (Menu 3-3)
Menu 2-5-1 Mode altern.
Selectbetweenvalues.Checkmarkshowscurrentsetting.
MODE POS: XXXXX Entry Default
fixed run time
Fixed frame heater on time
enthalpy-ctrl rtm Enthalpy control by ambient air temperature and
humidity