• Menu6-7-1SDSTEV
SDS TEV POS: XXXXX Entry Default
SDS TEV xx m Principle participation of the controller in the suction
pressure shift. (function COPT+). Note: This is
transmitted via a CAN bus telegram and intervenes in
the regulation!
, ,(ON/OFF)
OFF
Inact.a.Def xx m Delay time following completion of the defrost before the
controller actively intervenes in the shift.
0..40 30 min,
Dely_HystON xxxxm Delay time for the reduction request with active cooling
and overshoot of the hysteresis.
0..10 2.5 min
HiTmpZ1 dwn xxm Delay time before the elapse of the high temperature
alarm delay in zone 1, before the reduction is requested.
0..15 5 min.
HiTmpZ2 dwn xxm Delay time before the elapse of the high temperature
alarm delay in zone 2, before the reduction is requested.
0..15 5 min.
TolOvHystZ1 xxK Tolerance limit above the setpoint plus hysteresis in
zone 1. Influences when it is switched from stop to
reduce.
0..20 2 K
TolOvHystZ2 xxK Tolerance limit above the setpoint plus hysteresis in
zone 2. Influences when it is switched from stop to
reduce.
0..20 2 K
SwtchSupRet xxx Switching from supply air to return air and the reverse
with temperature alarm delay time.
, ,(ON/OFF)
OFF
Dely_Switch xxxm Switching from supply to return air: determines when it
is switched within the delay time for the high
temperature alarm.
0..15 5 min.
Add.Values xxx Creation of additional (additive) "Debug" actual value
archives in the system centre / store computer.
Warning: This can force a reorganisation of the actual
valuearchives–forthisreasononly use when required!
, ,(ON/OFF)
OFF
Incl_UpLim xxxK Upper limit of the neutral zone for determining the
incline.
0..5 0.3 K
Incl_LwLim xxxK Lower limit of the neutral zone for determining the
incline.
0..5 0.2 K