•
•
•
•
Menu2-1-2Zone2
COOLING 2 POS: XXXXX Entry Default
Setpoint R2.3 XXX °C Supply air temperature setpoint -20..20 -4 °C
Hystersis R2.3 X K Supply air temperature hysteresis setpoint 1..8 4 K
Setpoint R4.3 XXX °C Return air temperature setpoint for comparison -15..20 2 °C
Hystersis R4.3 X K Return air temperature hysteresis setpoint 1..8 2 K
Menu2-1-3Zone1AAltern.
COOLING 1A POS: XXXXX Entry Default
Setpoint R2.1 XXX °C Supply air temperature setpoint -20..20 -2 °C
Hystersis R2.1 X K Supply air temperature hysteresis setpoint 1..8 4 K
Setpoint R4.1 XXX °C Return air temperature setpoint for comparison -15..20 2 °C
Hystersis R4.1 X K Return air temperature hysteresis setpoint 1..8 2 K
Humid. On Time 0m Humidifier on time
Only shown when single-zone operation is set
(Menu 6-1)
--, 0..15 5 m
Menu2-1-4Zone2AAltern.
COOLING 2A POS: XXXXX Entry Default
Setpoint R2.3 XXX °C Supply air temperature setpoint -20..20 -2 °C
Hystersis R2.3 X K Supply air temperature hysteresis setpoint 1..8 4 K
Setpoint R4.3 XXX °C Return air temperature setpoint for comparison -15..20 2 °C
Hystersis R4.3 X K Return air temperature hysteresis setpoint 1..8 2 K
Menu2-2Defrost
DEFROST POS: XXXXX
1 Zone 1 Menu 2-2-1
2 Zone 2 Menu 2-2-2
Only shown when two-zone operation is set (Menu 6-1)
3 Zone 1A Altern. Menu 2-2-3
Not shown when setpoint toggle is disabled (Menu 3-3)
4 Zone 2A Altern. Menu 2-2-4
Only shown when two-zone operation is set (Menu 6-1) and setpoint toggle is not
disabled (Menu 3-3)